Fire Sprinkler and Alarm Permit in University Place, Washington

Required for automatic sprinkler and fire alarm systems in University Place, under the 2021 International Fire Code as heavily amended by UPMC 14.05.110.

Verified 2026-09-16 · Source

When you need this permit

  • “The 2021 Edition of the International Fire Code, including Appendix B” (UPMC 14.05.030), with amendments running to roughly half of Chapter 14.05
  • Sprinkler thresholds are lowered to 5,000 sq ft across Groups A-1 to A-4, B, E, F, M and S; 2,500 sq ft for two named uses
  • Alarm systems with 30+ actuating devices must be ADDRESSABLE; more than 75 smoke detectors or 200 total devices must be ANALOG INTELLIGENT
  • Existing systems are exempt unless a remodel or expansion exceeds 30 percent; above 50 percent, compliance is required “within 18 months of permit application”
  • A fire alarm panel must report a signal's location “written in English, not code” (added IFC 907.1.4)
  • Where a new building has a suppression system, an occupant notification alarm system must also be installed — including tenant improvements in sprinklered buildings (IFC 907.5 as amended)

Required documents

Check off what you have — your progress is saved on this device.

Fee schedule

Permit fee
UPMC 14.05.060: “All fee schedules shall be listed in a fee resolution adopted by the City Council of the City of University Place.” No dollar amount appears in the code. Show full citationUPMC 14.05.060: “All fee schedules shall be listed in a fee resolution adopted by the City Council of the City of University Place.” No dollar amount appears in the code. The fire code amendments add a parallel provision at IFC 105.2.15: “The City shall collect fees for permits, plan review and inspection services as prescribed in the City of University Place ‘Fee Schedule.’” Across this Washington set the instrument varies — resolution here and in Edmonds and Lake Stevens, a fee ORDINANCE in Lynnwood, an EXECUTIVE ORDER in Puyallup, a PUBLISHED TABLE in Issaquah, a master fee schedule in Longview, and nothing at all in Wenatchee.
Set by city council fee resolution
False alarm response
Added IFC Section 901.11: “In the event of more than two false alarms in any 90-day period the Chief may charge a fee for fire department response as specified in the City of University Place ‘Fee… Show full citationAdded IFC Section 901.11: “In the event of more than two false alarms in any 90-day period the Chief may charge a fee for fire department response as specified in the City of University Place ‘Fee Schedule.’” The panel must carry “an approved sign indicating such fees will be imposed.” No amount is published in the code.
Chargeable after 2 in any 90 days
Fire watchUPMC 14.05.110 amends IFC 901.7.0.1 so the Fire Code Official determines when a fire watch is required and “the person responsible for the facility shall pay a fee per the fee schedule for associated costs”, with a further fee where more than one person is required.
Facility pays per the fee schedule

Review timeline

Plan review
Not published — contact the department

How long did your Fire Sprinkler and Alarm Permit permit actually take in University Place?

Anonymous — one question, no email. Answers are combined and only shown once at least 5 people have reported.

Inspection process

    Tips

    • Your alarm technology is decided by device count before you choose a panel: 30 or more actuating devices forces an addressable system, and more than 75 smoke detectors or 200 total devices forces an analog intelligent one. Specify against those numbers rather than against the model code.
    • A remodel can drag an existing alarm system into compliance. Below 30 percent of the building nothing changes; above 50 percent the whole building must comply within 18 months of permit application — so a large tenant improvement carries a building-wide alarm obligation with a clock on it.
    • Budget for annunciation wording, oddly enough: the panel must give the signal location “written in English, not code”, which rules out the abbreviated device labels many installers default to.

    Frequently asked questions

    University Place requires a fire sprinkler and alarm permit for: “The 2021 Edition of the International Fire Code, including Appendix B” (UPMC 14.05.030), with amendments running to roughly half of Chapter 14.05; Sprinkler thresholds are lowered to 5,000 sq ft across Groups A-1 to A-4, B, E, F, M and S; 2,500 sq ft for two named uses; Alarm systems with 30+ actuating devices must be ADDRESSABLE; more than 75 smoke detectors or 200 total devices must be ANALOG INTELLIGENT; Existing systems are exempt unless a remodel or expansion exceeds 30 percent; above 50 percent, compliance is required “within 18 months of permit application”; A fire alarm panel must report a signal's location “written in English, not code” (added IFC 907.1.4); Where a new building has a suppression system, an occupant notification alarm system must also be installed — including tenant improvements in sprinklered buildings (IFC 907.5 as amended). If your project isn't listed, confirm with City of University Place at (253) 566-5656 before starting work.

    In University Place, the published Permit fee is: Set by city council fee resolution. Additional published fees: False alarm response — Chargeable after 2 in any 90 days; Fire watch — Facility pays per the fee schedule. These are the jurisdiction's own published figures — see the fee schedule table and source citations on this page.

    University Place does not publish a plan-review timeline for this permit. Contact City of University Place at (253) 566-5656 for current turnaround.

    Depending on your project, University Place may also ask for: Sprinkler System Plans; Fire Alarm System Plans; Fire Apparatus Access Plan. See the required-documents checklist on this page for details on each.

    Apply through City of University Place at 3609 Market Place West, Suite 200, University Place, WA 98466. Phone: (253) 566-5656. Official information: https://www.cityofup.com/.

    University Place, Washington has adopted: UPMC 14.05.030 opens: “The following codes are hereby adopted by this reference as if fully set forth in this chapter and as specifically modified or amended as set forth in this chapter:”; IBC — “The 2021 Edition of the International Building Code, including Appendix E, and ICC/ANSI A117.1-2017, and the 2021 International Existing Building Code and International Swimming Pool and Spa Code published by the International Code Council, is hereby adopted b…” (extract ends there). Three codes and an accessibility standard in one sentence.; IRC — “The 2021 Edition of the International Residential Code including Appendices F, Q and U as published by the International Code Council is hereby adopted as amended by the Washington State Building Code Council in Chapter 51-51 WAC…” Appendices F (Radon), Q (Tiny Houses) and U (Dwelling Unit Fire Sprinkler Systems) — the same three Issaquah takes, where Lake Stevens takes only F and Q.; IMC / FUEL GAS — “The 2021 Edition of the International Mechanical Code, including adoption of and amendments to the 2021 International Fuel Gas Code (NFPA 54), published by the International Code Council, and the 2021 Liquefied Petroleum Gas Code (NFPA 58), published by the National Fire Protection Association, is hereby adopted by reference with the exceptions noted in Chapter 5152 WAC.” NOTE TWO THINGS AS PUBLISHED: NFPA 58 is named at 2021 here, and the WAC chapter is printed “5152” without its hyphen.; IFC — “The 2021 Edition of the International Fire Code, including Appendix B, published by the International Code Council is hereby adopted by reference with the additions, deletions, and exceptions co…” and those amendments run to roughly half the chapter.; UPC — “The 2021 Edition of the Uniform Plumbing Code, including Appendices A, B, I and M, published by the International Association of Plumbing and Mechanical Officials, is hereby adopted by reference with the additions, deletions and exceptions contained in Chapter 51-56 WAC.” Four appendices, where Lake Stevens takes A, B and I.; ENERGY — “The 2021 Edition of the Washington State Energy Code, including commercial and residential provisions and appendices, is hereby adopted by reference with the additions, deletions and exceptions contained in Chapters 51-11C and 51-11R WAC.”; NO ELECTRICAL CODE APPEARS in the UPMC 14.05.030 list as read. The absence is bounded: the adoption paragraphs were read in sequence and cover the IBC/IEBC/ISPSC, IRC, IMC/IFGC/NFPA 58, IFC, UPC and energy code. Electrical permitting in Washington is the Department of Labor and Industries' under Chapter 19.28 RCW; this entry does not establish the arrangement for University Place.; NOT OPENED FOR THIS ENTRY: UPMC 14.10 (Moving of Buildings), 14.15 (Flood Damage Prevention), 14.20 (RETAINING WALLS — a whole chapter, §§ 14.20.010–.080, unusual to find separated out), UPMC 14.05.090 (Administrative provisions), 14.05.100 (Building code amendments), 14.05.120 (Penalties and enforcement), 14.05.130 (Liability), 14.05.140 (Hearings Examiner) and UPMC § 9.05.040, which the construction-hours section cross-references.. Local amendments apply — see the University Place overview page for the full list.

    It depends on how many devices you have, not on building size. Added IFC Section 907.1.5 provides that “all alarm systems, new or replacement, serving 30 or more alarm actuating devices, shall be addressable fire detection systems”, and that systems “serving more than seventy-five (75) smoke detectors or more than 200 total alarm activating devices shall be analog intelligent fire detection systems.” Existing systems need not comply unless a remodel or expansion exceeds 30 percent of the building, and where it exceeds 50 percent “the building must comply within 18 months of permit application.” Added Section 907.1.4 also requires the panel to give a signal's location “written in English, not code”.

    Sources & verification

    Verified against official sources. Last reviewed 2026-09-16.

    Fees, timelines, and adopted codes are researched from each jurisdiction's published records — see how we verify. Requirements change and vary by project, so always confirm the current details with the University Place building department before you submit. PermitBase is an independent reference and is not affiliated with any government agency.

    University Place's permit history isn't searchable here yet

    This page covers what the permit requires. What we don't have for University Place yet is the record of permits actually issued — the history you'd search by street address. That is a gap in our coverage, not a statement about any particular property.

    Your email, and the place — never an address. We only use it to tell you when University Place lands. Privacy.

    Compare fire sprinkler and alarm permit fees across Washington

    Look up this fee in a different city →

    Embed this data card →

    Now live

    Build your University Place project checklist

    Describe your project once and get every permit, document, and fee it triggers in University Place — in one checklist. Free, for any city and any number of projects.

    Get started →