Skip to main content
PermitBase

Fire Sprinkler & Fire Alarm System Permit in Washington Terrace, Utah

Washington Terrace has no standalone fire-sprinkler or fire-alarm permit type or fee line. The city's own Fire/Rescue department (Washington Terrace Fire/Rescue, 4601 South 300 West; Business Fire Inspections 801-393-6349) is an independent city department, not a joint fire district — but neither the FY 2026-27 Consolidated Fee Schedule (Resolution 26-08, checked page-by-page 2026-07-22) nor the Fire/Rescue department page (washingtonterrace.gov/fire) publishes a distinct sprinkler or alarm fee; this work is filed and priced through the same general Building/Excavation Permit process as other trade work (Municipal Code § 15.02.020), which the city's own Municipal Code Chapter 15.08 (International Fire Code) also separately adopts by reference (§ 15.08.010: 'The International Fire Code ... in its most current edition as adopted by the state ... is adopted ... and incorporated in this code'). Independent of the city process, Utah's State Fire Code Act (Utah Code §§ 15A-5-101 to -103) adopts the 2024 International Fire Code statewide, and IFC § 106.1 as amended by Utah Code § 15A-5-202(1)(c) requires that 'Fire sprinkler system layout shall be prepared and submitted by a person certified by the National Institute for Certification in Engineering Technologies (NICET) at level III or IV in Water-Based System Layout,' and fire alarm system layout by a NICET level III/IV Fire Alarm Systems-certified person. As a result, sprinkler and alarm plans in Washington Terrace are also independently reviewable by the Utah State Fire Marshal's Office (SFMO) using the SFMO's own statewide submittal forms and fee (square footage x $0.022, $75 minimum), separate from whatever the city's Building Department or Washington Terrace Fire/Rescue charges through the general building permit.

Verified 2026-07-22 · Source

When you need this permit

  • Installation, alteration, or extension of an automatic fire sprinkler system (NFPA 13/13R/13D) or a fire alarm/detection system (NFPA 72), filed as a Building/Excavation Permit since no dedicated local fire-system permit track exists, per Municipal Code § 15.02.010
  • Comply with the International Fire Code as adopted by Washington Terrace Municipal Code § 15.08.010 (adopting 'the most current edition as adopted by the state,' currently the 2024 IFC per Utah Code § 15A-5-103) and its local appendix amendments in § 15.08.020
  • One- and two-family dwellings: per Municipal Code § 15.08.020(3)(a) (IFC Appendix B105.1, as locally amended), a fire sprinkler system is not required where the required fire flow and flow duration are met for a dwelling with a fire area up to 3,600-5,000 sq ft; larger fire areas require the flow specified in Table B105.1, which in practice may require a sprinkler system if adequate fire flow/hydrants are unavailable
  • Fire sprinkler system drawings must be prepared and submitted by a person NICET-certified at level III or IV in Water-Based System Layout; fire alarm system drawings by a person NICET-certified at level III or IV in Fire Alarm Systems, per IFC § 106.1 as amended by Utah Code § 15A-5-202(1)(c)
  • Water supply analysis (static pressure, residual pressure, flow in gpm) must be provided per Utah Admin. Code R710-4-5, sourced from contract specifications, a water supply analysis, or the water purveyor
  • Separate, parallel plan-review submittal to the Utah State Fire Marshal's Office is required for the sprinkler and/or alarm system plans, in addition to whatever the city's Building Department requires for the underlying building permit

Required documents

Check off what you have — your progress is saved on this device.

Not ready yet0 of 3 required documents checked.

This checker covers one permit. A full project usually triggers several — our paid checklist will assemble all of them, from $29

Fee schedule

Building Permit Fee — valuation-based (ICC Building Valuation Data)Washington Terrace Municipal Code § 15.02.020 — the same fee mechanism used for every other permit type in this file; no separate sprinkler/alarm valuation or flat fee is published by the city (FY 2026-27 Consolidated Fee Schedule read page-by-page 2026-07-22; no Fire line item found).
Set by the 'Building Permit Fee Schedule' in the most current adopted code edition, applied to project valuation from the ICC 'Building Valuation Data' table.
Plan Review Fee (residential 25% / commercial 65%)Washington Terrace City FY 2026-27 Consolidated Fee Schedule (Resolution 26-08, adopted 6/26), 'Building Permits (3.2).' The schedule does not break out a separate rate for fire-protection scope; the same residential/commercial split used elsewhere in this file applies.
25% of the building permit fee for single/multiple-family permits; 65% for commercial permits
State SurchargeWashington Terrace Municipal Code § 15.02.040, imposed under Utah Code Ann. § 58-56-9(4).
1% of building permit fee
State Fire Marshal Plan Review Fee — Automatic Fire Sprinkler SystemUtah State Fire Marshal's Office 'Automatic Fire Sprinkler Plan Submittal Form' (current as of 2026-07-22; downloaded and read directly): 'SQUARE FEET x .022$ = $______ Note: Minimum fee is $75.' Fees must be paid before plan review is released. Payable to the Utah State Fire Marshal's Office, 410 West 9800 South, 3rd Floor, Sandy, UT 84070 (planreviews@utah.gov, 801-256-2390) — separate from, and in addition to, any fee charged by the City of Washington Terrace.
Scope-of-work square footage x $0.022 per sq ft; minimum fee $75.00
State Fire Marshal Plan Review Fee — Fire Alarm SystemUtah State Fire Marshal's Office 'Fire Alarm Plan Review Submittal Form' (current as of 2026-07-22; downloaded and read directly): identical formula and minimum fee to the sprinkler submittal form. Fees must be paid before plan review is released.
Scope-of-work square footage x $0.022 per sq ft; minimum fee $75.00

Review timeline

Plan review
Not published — contact the department

How long did your Fire Sprinkler & Fire Alarm System Permit permit actually take in Washington Terrace?

Anonymous — one question, no email. Answers are combined and only shown once at least 5 people have reported.

Inspection process

  1. 1

    Fire Sprinkler/Alarm Rough-In and Final Inspection

    Performed by Washington Terrace Fire/Rescue (Business Fire Inspections line, 801-393-6349) and/or the Chief Building Official, verifying compliance with the adopted IFC (Municipal Code § 15.08) and NFPA 13/72 as applicable, in coordination with the underlying building permit's inspection schedule.

  2. 2

    Annual Testing and Inspection (post-installation)

    After acceptance, automatic fire sprinkler systems require ongoing inspection/testing per Utah Admin. Code R710-5 and fire alarm systems per R710-11, performed and tagged by a state-certified technician; this is a recurring life-safety requirement, not a one-time permit inspection.

See the full Washington Terrace inspection guide — scheduling & re-inspection fees →

Tips

  • Washington Terrace is not served by a joint fire district (unlike several neighboring Weber County cities served by Weber Fire District) — it maintains its own city Fire/Rescue department. Even so, neither the city's own Consolidated Fee Schedule nor its Municipal Code publishes a distinct sprinkler or alarm fee; this is a genuine gap in local publication, not a joint-district omission.
  • Fire sprinkler and fire alarm plans in Utah are subject to a separate, parallel plan-review submittal to the Utah State Fire Marshal's Office, with its own fee (square footage x $0.022, $75 minimum) — this is independent of and in addition to whatever the City of Washington Terrace charges through the general Building Permit process. Out-of-state designers in particular tend to miss this requirement.
  • Sprinkler layouts must be prepared by a NICET III/IV Water-Based System Layout-certified person and alarm layouts by a NICET III/IV Fire Alarm Systems-certified person, per IFC § 106.1 as amended by Utah Code § 15A-5-202(1)(c) — a project cannot avoid this by using an uncertified designer even if the city's own review is otherwise satisfied.
  • Confirm current sprinkler/alarm fee handling directly with Washington Terrace Fire/Rescue at 801-393-6349 before budgeting a commercial fire-protection project — the city's silence on a distinct fee does not necessarily mean $0; it likely means the cost is folded into the general commercial Building Permit's 65% plan-review fee.

Frequently asked questions

Washington Terrace requires a fire sprinkler & fire alarm system permit for: Installation, alteration, or extension of an automatic fire sprinkler system (NFPA 13/13R/13D) or a fire alarm/detection system (NFPA 72), filed as a Building/Excavation Permit since no dedicated local fire-system permit track exists, per Municipal Code § 15.02.010; Comply with the International Fire Code as adopted by Washington Terrace Municipal Code § 15.08.010 (adopting 'the most current edition as adopted by the state,' currently the 2024 IFC per Utah Code § 15A-5-103) and its local appendix amendments in § 15.08.020; One- and two-family dwellings: per Municipal Code § 15.08.020(3)(a) (IFC Appendix B105.1, as locally amended), a fire sprinkler system is not required where the required fire flow and flow duration are met for a dwelling with a fire area up to 3,600-5,000 sq ft; larger fire areas require the flow specified in Table B105.1, which in practice may require a sprinkler system if adequate fire flow/hydrants are unavailable; Fire sprinkler system drawings must be prepared and submitted by a person NICET-certified at level III or IV in Water-Based System Layout; fire alarm system drawings by a person NICET-certified at level III or IV in Fire Alarm Systems, per IFC § 106.1 as amended by Utah Code § 15A-5-202(1)(c); Water supply analysis (static pressure, residual pressure, flow in gpm) must be provided per Utah Admin. Code R710-4-5, sourced from contract specifications, a water supply analysis, or the water purveyor; Separate, parallel plan-review submittal to the Utah State Fire Marshal's Office is required for the sprinkler and/or alarm system plans, in addition to whatever the city's Building Department requires for the underlying building permit. If your project isn't listed, confirm with Washington Terrace City Building, Planning & Inspection Department at (801) 395-8288 before starting work.

No distinct city fee line exists — the FY 2026-27 Consolidated Fee Schedule and Municipal Code are silent on a specific sprinkler/alarm fee, so this work is filed and priced through the general Building/Excavation Permit (valuation-based fee plus the 25%/65% plan review rate). Separately, Utah law requires fire sprinkler and fire alarm plans to also be submitted to the Utah State Fire Marshal's Office for review, with its own fee of $0.022 per square foot (minimum $75), regardless of what the city charges.

Washington Terrace does not publish a plan-review timeline for this permit. Contact Washington Terrace City Building, Planning & Inspection Department at (801) 395-8288 for current turnaround.

You'll need: Building/Excavation Permit Application; Automatic Fire Sprinkler Plan Submittal Form (Utah State Fire Marshal's Office); Fire Alarm Plan Review Submittal Form (Utah State Fire Marshal's Office). See the required-documents checklist on this page for details on each.

Washington Terrace requires 2 inspection(s) for a fire sprinkler & fire alarm system permit, in order: Fire Sprinkler/Alarm Rough-In and Final Inspection, Annual Testing and Inspection (post-installation). Schedule each through Washington Terrace City Building, Planning & Inspection Department ((801) 395-8288).

Apply through Washington Terrace City Building, Planning & Inspection Department at 5249 South 400 East, Washington Terrace, UT 84405. Phone: (801) 395-8288, email: Tylers@washingtonterracecity.org. Office hours: Mon–Fri 8:00 AM – 5:00 PM (Closed Holidays). Official information: https://washingtonterrace.gov/building.

Washington Terrace, Utah has adopted: International Building Code (IBC), most current edition — adopted by reference per Washington Terrace Municipal Code § 15.04.010(1)(a), automatically updated whenever the Utah Uniform Building Code Commission adopts a new edition (§ 15.04.060); currently the 2024 IBC per Utah Code § 15A-2-103, effective statewide July 1, 2026.; International Residential Code (IRC), most current edition — incorporated via IBC reference per § 15.04.010(1)(a); currently the 2021 IRC per Utah Code § 15A-2-103 (unchanged in the July 1, 2026 statewide update).; International Energy Conservation Code (IECC), most current edition — incorporated via IBC reference per § 15.04.010(1)(a); currently the 2024 IECC per Utah Code § 15A-2-103, effective statewide July 1, 2026 (statewide residential energy provisions effectively follow 2015 IECC residential per § 15A-2-104).; National Electrical Code (NEC), most current edition, as promulgated by NFPA — adopted per § 15.04.010(1)(b), amended per Utah Admin. Code R156-56-705; currently the 2023 NEC.; International Plumbing Code (IPC), most current edition — adopted per § 15.04.010(1)(c), amended per Utah Admin. Code R156-56-706; currently the 2024 IPC per Utah Code § 15A-2-103, effective statewide July 1, 2026.; International Mechanical Code (IMC) and International Fuel Gas Code (IFGC), most current editions — adopted per § 15.04.010(1)(d), amended per Utah Admin. Code R156-56-704; currently the 2024 IMC/IFGC per Utah Code § 15A-2-103, effective statewide July 1, 2026.; International Existing Building Code (IEBC) — adopted per Washington Terrace Municipal Code § 15.06.010.; Uniform Housing Code, Uniform Code for Abatement of Dangerous Buildings, and Uniform Code for Building Conservation — adopted per §§ 15.06.020–15.06.040.; All codes are automatically updated per § 15.04.060 whenever the Utah Division of Occupational and Professional Licensing (DOPL) or Uniform Building Code Commission adopts a new edition, per Utah Code § 58-56-4(3) — Washington Terrace does not maintain a separately-dated local code adoption; it tracks the statewide edition in force.. Local amendments apply — see the Washington Terrace overview page for the full list.

Both. Washington Terrace Fire/Rescue and the Chief Building Official are involved through the standard building permit process, and Utah Code § 15A-5-202(1)(c) separately requires NICET-certified sprinkler/alarm layouts to go through the Utah State Fire Marshal's Office's own plan-review submittal, in addition to any local review.