Fire Sprinkler System Permit (NFPA 13 / NFPA 13R) in Unincorporated Clark County, Nevada

Required for installation of automatic fire sprinkler systems in unincorporated Clark County, issued by the Clark County Fire Department (CCFD) Fire Prevention Bureau — a separate submittal track from the Department of Building's construction permits. Design must follow NFPA 13 (commercial) or NFPA 13R (low-rise residential occupancies) as amended by the Clark County Fire Code (CCFC), per IFC §105.7.1 and §903.3.1.2.

Reviewed 2026-07-22 · Source

When you need this permit

  • A permit is required for installation of any automatic fire sprinkler system per IFC §105.7.1 as adopted and amended by the Clark County Fire Code
  • Design must comply with NFPA 13 (commercial) or NFPA 13R (low-rise residential occupancies), 2016 edition as referenced in CCFD's current posted permit guide and as further amended by the CCFC
  • Plans must be prepared to an architectural scale, sized 30" x 42", and submitted as consolidated PDFs electronically via the Citizen Access Portal — paper plans are no longer accepted
  • Complete hydraulic calculations are required per NFPA 13R §8.2.1 (referencing NFPA 13 §23.3.5)
  • Manufacturer's specification sheets required for all system components
  • Plans must be reviewed and signed by a NICET Level 2 Designer in Water-Based Fire Protection Systems, or a Nevada-registered Professional Engineer working in their area of expertise; submittals must include the designer's name, certification number and signature, the licensee's name, contractor's license number, and NSFM (Nevada State Fire Marshal) number Contractor
  • Supporting documentation required where applicable: approved civil plans, an approved Fire Protection Report (FPR) or Alternative Materials and Methods Report (AMMR), the originally approved plans, flow test results, a Water Purveyor letter (for antifreeze systems), and fire pump acceptance test results
  • Revisions made after plan approval must be submitted (clouded and keyed to a Plan Revision number) and approved before final system acceptance

Required documents

Check off what you have — your progress is saved on this device.

Not ready yet0 of 3 required documents checked.

This checker covers one permit. A full project usually triggers several — our checklist will assemble all of them, free →

Fee schedule

Fire Sprinkler Permit Fee — fewer than 20 headsClark County Fire Code, Table 106-F (Fire Protection Systems), per up.codes' hosted copy of the currently adopted Clark County Fire Code text; this figure is not independently confirmed against a live.gov/Municode page — treat as a real but not fully cross-verified fee.
$6.00 per 1,000 sq ft
Fire Sprinkler Permit Fee — 20 or more headsClark County Fire Code, Table 106-F. Same sourcing caveat as above.
$20.00 per 1,000 sq ft
Minimum Permit FeeClark County Fire Code, Table 106-A — floor fee applied when the calculated square-footage-based fee falls below this amount. Same sourcing caveat as above.
$90.00
Fire Protection Report (FPR) review — Non-Expedite, Initial Submittal
A separate fee from the sprinkler permit itself; Show full citationA separate fee from the sprinkler permit itself; applies only when a project also requires a Fire Protection Report/Life Safety Package (high-rise, covered mall, atrium, or other complex/major facility, or certain remodel scenarios per CCFD's Fire Protection Report Submittal Guideline). Expedited review is $300 plus $85/hr of plan review.
$150.00

Review timeline

Plan review
Not published — contact the department

How long did your Fire Sprinkler System Permit (NFPA 13 / NFPA 13R) permit actually take in Unincorporated Clark County?

Anonymous — one question, no email. Answers are combined and only shown once at least 5 people have reported.

Inspection process

  1. 1

    Underground / Mains

    Underground fire sprinkler piping and mains inspected before backfill

  2. 2

    Rough-In / Hydrostatic Test

    Overhead piping rough-in and hydrostatic pressure test before concealment

  3. 3

    Final / Acceptance Test

    Full system flow test, alarm/flow-switch verification, and fire department connection check before system acceptance

See the full Unincorporated Clark County inspection guide — scheduling & re-inspection fees →

Tips

  • Fire sprinkler permits are issued by CCFD Fire Prevention through the Citizen Access Portal — a distinct submittal from the Building Department's construction permit for the same project; permit numbers begin with 'FP' (e.g., FP20-00000).
  • Paper plan submittals are no longer accepted — all plans, calculations, and supporting documents must be consolidated into PDFs and uploaded electronically.
  • Revisions made after approval must be clouded and keyed to a Plan Revision number, and must be approved before final system acceptance — this is separate from a corrections re-submittal.
  • A prepaid account option is available through CCFD for contractors who submit frequently, allowing fees to be drawn from a standing balance rather than paid per submittal.

Frequently asked questions

Unincorporated Clark County requires a fire sprinkler system permit (nfpa 13 / nfpa 13r) for: A permit is required for installation of any automatic fire sprinkler system per IFC §105.7.1 as adopted and amended by the Clark County Fire Code; Design must comply with NFPA 13 (commercial) or NFPA 13R (low-rise residential occupancies), 2016 edition as referenced in CCFD's current posted permit guide and as further amended by the CCFC; Plans must be prepared to an architectural scale, sized 30" x 42", and submitted as consolidated PDFs electronically via the Citizen Access Portal — paper plans are no longer accepted; Complete hydraulic calculations are required per NFPA 13R §8.2.1 (referencing NFPA 13 §23.3.5); Manufacturer's specification sheets required for all system components; Plans must be reviewed and signed by a NICET Level 2 Designer in Water-Based Fire Protection Systems, or a Nevada-registered Professional Engineer working in their area of expertise; submittals must include the designer's name, certification number and signature, the licensee's name, contractor's license number, and NSFM (Nevada State Fire Marshal) number; Supporting documentation required where applicable: approved civil plans, an approved Fire Protection Report (FPR) or Alternative Materials and Methods Report (AMMR), the originally approved plans, flow test results, a Water Purveyor letter (for antifreeze systems), and fire pump acceptance test results; Revisions made after plan approval must be submitted (clouded and keyed to a Plan Revision number) and approved before final system acceptance. If your project isn't listed, confirm with Clark County Building & Fire Prevention Department at (702) 455-3000 before starting work.

In Unincorporated Clark County, the published Fire Sprinkler Permit Fee — fewer than 20 heads is: $6.00 per 1,000 sq ft. Additional published fees: Fire Sprinkler Permit Fee — 20 or more heads — $20.00 per 1,000 sq ft; Minimum Permit Fee — $90.00; Fire Protection Report (FPR) review — Non-Expedite, Initial Submittal — $150.00. These are the jurisdiction's own published figures — see the fee schedule table and source citations on this page.

Unincorporated Clark County does not publish a plan-review timeline for this permit. Contact Clark County Building & Fire Prevention Department at (702) 455-3000 for current turnaround.

You'll need: Fire Sprinkler System Plans; Hydraulic Calculations; Material/Equipment Specification Sheets. Depending on your project, Unincorporated Clark County may also ask for: Supporting Documentation. See the required-documents checklist on this page for details on each.

Unincorporated Clark County requires 3 inspection(s) for a fire sprinkler system permit (nfpa 13 / nfpa 13r), in order: Underground / Mains, Rough-In / Hydrostatic Test, Final / Acceptance Test. Schedule each through Clark County Building & Fire Prevention Department ((702) 455-3000).

Apply through Clark County Building & Fire Prevention Department at 4701 West Russell Road, Las Vegas, NV 89118. Phone: (702) 455-3000, email: pacenter@ClarkCountyNV.gov. Office hours: Mon–Thu 7:30 AM – 5:30 PM (closed Fri, Sat, Sun). Official information: https://www.clarkcountynv.gov/government/departments/building___fire_prevention/.

NFPA 13 governs most commercial sprinkler systems, while NFPA 13R applies to qualifying low-rise residential occupancies, both as amended by the Clark County Fire Code. CCFD's posted permit guide for NFPA 13R currently references the 2016 edition of NFPA 13R; confirm the current amended requirements with CCFD Fire Prevention (702-455-7100) before finalizing design.

No. CCFD requires electronic PDF submittal of all plans, hydraulic calculations, material data, and supporting documents through the Citizen Access Portal.

Sources & verification

Key facts verified against official sources. Last reviewed 2026-07-22.

Fees, timelines, and adopted codes are researched from each jurisdiction's published records — see how we verify. Requirements change and vary by project, so always confirm the current details with the Unincorporated Clark County building department before you submit. PermitBase is an independent reference and is not affiliated with any government agency.

Unincorporated Clark County's permit history isn't searchable here yet

This page covers what the permit requires. What we don't have for Unincorporated Clark County yet is the record of permits actually issued — the history you'd search by street address. That is a gap in our coverage, not a statement about any particular property.

Your email, and the place — never an address. We only use it to tell you when Unincorporated Clark County lands. Privacy.