Fire Sprinkler & Fire Alarm Permit (Fire Code Review) — Winnemucca, Nevada · Requirements sheet
Reviewed 2026-07-22 · Source: https://www.humboldtcountynv.gov/DocumentCenter/View/3385/Commercial-Projects-Handout-4-19
PermitBase is an independent reference and is not affiliated with any government agency. Requirements change and vary by project — confirm current details with the building department before you submit.
Fire Sprinkler & Fire Alarm Permit (Fire Code Review) in Winnemucca, Nevada
Automatic sprinkler and fire alarm system installations in Winnemucca are reviewed through 'Fire Code Review,' performed by the Humboldt County Building & Safety Department on behalf of the Nevada State Fire Marshal's office, using a shared 'Application for Fire Code Plan Review' form (with checkboxes for Automatic Sprinkler, Fire Alarm, Extinguishing System (non-sprinkler), Architectural/Construction, or Other) plus system-specific submittal checklists — a 48-item 'Submittal List for Automatic Sprinkler System' and a 19-item 'Submittal List for Fire Alarm Systems.' This review must be completed before a final inspection can be requested on the underlying building permit.
Reviewed 2026-07-22 · Source
When you need this permit
- A fire code review permit is required for automatic sprinkler system and/or fire alarm system installations in commercial/industrial buildings, per the City of Winnemucca / Humboldt County 'Commercial/Industrial Guide for Building Permit Applications': 'This review will be completed by the Humboldt County Building & Safety Department and is required to be completed before a final inspection is requested'
- Sprinkler systems: commercial systems designed to NFPA 13 (residential-type systems to NFPA 13D/13R), per 2018 IFC Section 903 and Nevada Administrative Code (NAC) 477, per the live 'Submittal List for Automatic Sprinkler System' and the current (4-19 edition) Commercial/Industrial Guide. Fire alarm systems: designed to NFPA 72 and the IFC, per the live 'Submittal List for Fire Alarm Systems'
- CODE-EDITION NOTE (same drift pattern already documented elsewhere in this file): the two fire submittal-list handouts (Fire Alarm Submittal List, Fire Sprinkler Submittal List), both dated 10-13, reference the 2012 IFC — matching this file's codesAdopted entry and the 2026-07-16 RESOLUTION note confirming Winnemucca Municipal Code 15.04.140 still codifies the 2012 IFC. But the live Commercial/Industrial Guide (dated 4-19) references the 2018 IFC for the same fire code review process. This is the identical unreconciled City-ordinance-vs-department-handout conflict already documented for the IBC/IRC/NEC/UMC/UPC elsewhere in this file — confirm the applicable edition with the Building & Safety Department before design
- Sprinkler plan submittals must include (per the 48-item county checklist): full hydraulic calculations, pipe type/schedule/sizing, sprinkler make/type/model/K-factor, water supply source and pressure/elevation data, control/check valve and drain locations, and the NFPA 13 edition year the system is designed to, among other items
- Fire alarm plan submittals must include (per the 19-item county checklist): floor plans showing device locations with a device legend, alarm control/annunciation equipment, battery calculations, conductor type/sizing, voltage-drop calculations, and monitoring information
- Plans must be designed and signed by a Nevada State Fire Marshal-licensed fire alarm/sprinkler company (with license number) or by a Nevada-licensed fire protection engineer, and wet-stamped to comply with NRS 623, 624, and 625
- Buildings over 5,000 square feet are required to comply with NAC 477.920 (automatic sprinkler system required, subject to exceptions), per the Commercial/Industrial Guide's Fire Code Review section
- Where hazardous, combustible, or flammable materials are stored or used, MSDS sheets must be submitted and a separate hazardous materials storage permit may be required from the Nevada State Fire Marshal (HAZMAT line: 775-687-4290)
- The fire code review plan check fee is due upon completion of the review (amount not published — see fees below); approval by the appropriate Fire District Chief is also required if applicable
Required documents
Check off what you have — your progress is saved on this device.
Not ready yet — 0 of 1 required documents checked.
This checker covers one permit. A full project usually triggers several — our paid checklist will assemble all of them, from $29 →
Fee schedule
Review timeline
Inspection process
- 1
Fire System Final Inspection
Sprinkler and/or fire alarm system verified installed per the approved NFPA 13/NFPA 72 plans before the underlying building permit's final inspection and certificate of occupancy are issued; no separate published rough-in/final inspection sequence specific to fire systems was found beyond this general final-inspection requirement.
See the full Winnemucca inspection guide — scheduling & re-inspection fees →
Tips
- Fire code review is a distinct submittal from the general building permit review — plan on submitting a full separate set of plans using the 'Application for Fire Code Plan Review' form in addition to the general Building Permit application.
- Buildings over 5,000 square feet require an automatic sprinkler system per NAC 477.920 (subject to exceptions) — confirm whether your project's square footage triggers this state-level requirement.
- All fire alarm, sprinkler, and extinguisher contractors must hold a Nevada State Fire Marshal license; sprinkler/alarm plans may alternatively be designed by a Nevada-licensed fire protection engineer.
- Confirm which International Fire Code edition (2012 per the City's own codified ordinance, versus 2018 per the live department handout) your project will be reviewed against — this file documents the same unreconciled conflict for every other adopted code in Winnemucca.
Frequently asked questions
Sources & verification
Key facts verified against official sources. Last reviewed 2026-07-22.
Fees, timelines, and adopted codes are researched from each jurisdiction's published records — see how we verify. Requirements change and vary by project, so always confirm the current details with the Winnemucca building department before you submit. PermitBase is an independent reference and is not affiliated with any government agency.
Other permits in Winnemucca
Fire Sprinkler & Fire Alarm Permit (Fire Code Review) in other cities
Compare fire sprinkler & fire alarm permit (fire code review) fees across Nevada →
Look up this fee in a different city →
Now live
Build your Winnemucca project checklist
Describe your project once and get every permit, document, and fee it triggers in Winnemucca — in one checklist. Sign up and pay once to generate it, or go unlimited with Pro.
Get started →