Fire Sprinkler System / Fire Alarm & Detection System Permit — Unincorporated Bernalillo County, New Mexico · Requirements sheet
Verified 2026-07-22 · Source: https://www.bernco.gov/fire/wp-content/uploads/sites/74/2021/04/Plan_Review_Requirements_2020_2015IFC.pdf
PermitBase is an independent reference and is not affiliated with any government agency. Requirements change and vary by project — confirm current details with the building department before you submit.
Fire Sprinkler System / Fire Alarm & Detection System Permit in Unincorporated Bernalillo County, New Mexico
Fire protection system permits (automatic fire sprinkler systems and fire alarm/detection systems) in unincorporated Bernalillo County are administered separately from Planning & Development Services building permits — by the Bernalillo County Fire Department's Fire Marshal's Office (Fire Prevention Bureau), under the 2015 International Fire Code as locally amended March 24, 2020. Both system types are selected as 'Permit Type' options on the same BCFD Fire Protection Permit Application, alongside other fire-protection permit types (fire pump, hood & duct fire system, stand-pipe, etc.).
Verified 2026-07-22 · Source
When you need this permit
- All applicants/installing contractors must possess a current Certificate of Fitness from the New Mexico State Fire Marshal's Office; submittals from applicants without a valid Certificate of Fitness are denied and returned
- Fire Sprinkler and Fire Alarm plans must be submitted bearing a review certificate and signature of a New Mexico Licensed Professional/Fire Protection Engineer, per NMAC Title 16, Chapter 39, Part III, Subsection G ('Fire Protection Engineers')
- Automatic fire sprinkler systems must be designed per NFPA 13, 13D, or 13R as applicable, in accordance with the 2015 International Fire Code as amended; fire alarm/detection systems must be designed per NFPA 72
- The original design must be produced by at minimum a NICET Level IV Technician employed by the contracted installer, then reviewed and stamped by the licensed PE
- One (1) set of construction documents/shop drawings must be submitted on CD or DVD in PDF format, plus a minimum of one (1) paper/hard copy set at minimum 24 in x 36 in; approved hard copies not picked up within 10 business days of approval notification are destroyed
Required documents
Check off what you have — your progress is saved on this device.
Not ready yet — 0 of 3 required documents checked.
This checker covers one permit. A full project usually triggers several — our paid checklist will assemble all of them, from $29 →
Fee schedule
Review timeline
Inspection process
- 1
Final Installation Approval
Before requesting final approval, the installing contractor must furnish a written statement to the fire code official that the fire protection system was installed per the approved plans and tested per the manufacturer's specifications and the appropriate installation standard; any deviations must be noted with approvals attached
- 2
Fire Alarm Final Inspection / Acceptance Test
Required prior to building occupancy for fire alarm/detection systems specifically — a Record of Completion (NFPA 72 Ch. 1 Sec. 1.7.2.1) and as-built plans must be available; the acceptance test verifies initiating devices, control panels, and appliances, with smoke detectors tested using 'test smoke'
See the full Unincorporated Bernalillo County inspection guide — scheduling & re-inspection fees →
Tips
- The Fire Marshal's Office (Fire Prevention Bureau, 6840 Second St NW, 505-468-1310) is a separate department from Planning & Development Services Building Safety Division — its fire-protection plan review fees are published in its own 'Plans Review and Submittal Requirements' manual, not in Administrative Resolution 25-2009's Tables 3-A through 3-F.
- Only one permit type may be selected per Fire Protection Permit Application — a project needing both a sprinkler permit and a fire alarm permit needs two separate application submittals.
- All fire protection plans (sprinkler and alarm alike) must be submitted on CD/DVD in PDF format plus at least one 24x36 in hard copy; approved hard copies not picked up within 10 business days of approval notification are destroyed and would need to be resubmitted.
- Fire alarm systems require a dedicated electrical service for all main control panels, protective guards on circuit breakers, and (per NFPA 72) compliance with the most current NFPA edition referenced by the Bernalillo County Fire Code.
Frequently asked questions
Sources & verification
Verified against official sources. Last reviewed 2026-07-22.
Fees, timelines, and adopted codes are researched from each jurisdiction's published records — see how we verify. Requirements change and vary by project, so always confirm the current details with the Unincorporated Bernalillo County building department before you submit. PermitBase is an independent reference and is not affiliated with any government agency.
Other permits in Unincorporated Bernalillo County
Fire Sprinkler System / Fire Alarm & Detection System Permit in other cities
Compare fire sprinkler system / fire alarm & detection system permit fees across New Mexico →
Look up this fee in a different city →
Now live
Build your Unincorporated Bernalillo County project checklist
Describe your project once and get every permit, document, and fee it triggers in Unincorporated Bernalillo County — in one checklist. Sign up and pay once to generate it, or go unlimited with Pro.
Get started →