Fire Sprinkler & Fire Alarm System Permit (Santa Fe County Fire Department — Fire Prevention/Risk Reduction Division) in Edgewood, New Mexico

Installation, modification, or repair of a fire sprinkler system or a fire alarm/detection system within a building in the Town of Edgewood is regulated by the Santa Fe County Fire Department (SFCFD) Fire Prevention/Risk Reduction Division rather than by the Town, because Edgewood has no fire marshal or fire-code enforcement office of its own. SFCFD's own website states it 'protects approximately 1900 square miles of unincorporated area as well as the incorporated Town of Edgewood.' The Town's Planning & Zoning page lists the 2015 International Fire Code as the only building-related code directly adopted by the Town (see this file's codesAdopted); SFCFD's Fire Prevention/Risk Reduction Division is the office that actually administers plan review, permitting, and inspection for fire protection systems under that code for the Edgewood area, the same way CID stands in for a missing Town building department for other construction permits.

Verified 2026-07-22 · Source

When you need this permit

  • Three full-size sets of plans required for review, for both sprinkler systems (residential or commercial) and fire alarm/detection systems, plus cut sheets for all components/devices/appurtenances (SFCFD Fire Protection Systems Submittal & Inspection Guidelines)
  • Commercial sprinkler plans additionally require hydraulic calculations and a design-area notation; fire alarm plans additionally require voltage-drop calculations, battery details/calculations, and a system inputs-and-outputs matrix
  • Plans must be stamped by a NICET Level III or IV technician AND a New Mexico-certified engineer or NM-certified Fire Protection Engineer (alternative fire suppression systems may instead be stamped by NICET III/IV or a NM Certified Fire Protection Engineer alone)
  • Full payment is required before plans are accepted for review — accepted forms are Visa, MasterCard, Discover, check, money order, or cashier's check; cash is not accepted
  • The SFCFD-stamped set of plans must be present on site at every inspection, or the inspection will not be performed
  • Sprinkler systems require both a rough-in inspection and a final inspection; fire alarm and alternative suppression systems require a final inspection only
  • Both the fire alarm and sprinkler final inspections must be completed before a Certificate of Occupancy is released

Required documents

Check off what you have — your progress is saved on this device.

Not ready yet0 of 3 required documents checked.

This checker covers one permit. A full project usually triggers several — our paid checklist will assemble all of them, from $29

Fee schedule

Commercial Automatic Sprinkler (plan review/permit)Santa Fe County Fee Schedule for Fire Inspection & Plan Review (santafecountynm.gov/fire), current as of this research pass.
$200.00
Residential Automatic Sprinkler (plan review/permit)Santa Fe County Fee Schedule for Fire Inspection & Plan Review.
$75.00
Commercial Fire Alarm/Detection (plan review/permit)Santa Fe County Fee Schedule for Fire Inspection & Plan Review.
$150.00
Resubmission (fire protection system plans)Santa Fe County Fee Schedule for Fire Inspection & Plan Review — charged if submitted plans are rejected and must be resubmitted.
$50.00

Review timeline

Plan review
Not published — contact the department

How long did your Fire Sprinkler & Fire Alarm System Permit (Santa Fe County Fire Department — Fire Prevention/Risk Reduction Division) permit actually take in Edgewood?

Anonymous — one question, no email. Answers are combined and only shown once at least 5 people have reported.

Inspection process

  1. 1

    Rough-in Inspection (Sprinkler)

    Required before concealment of sprinkler piping; the SFCFD-stamped plan set must be on site or the inspection will not be performed.

  2. 2

    Final Inspection (Sprinkler)

    Installation company representative must be present; requires a signed Contractor's Material & Test Certificate for Above Ground Piping.

  3. 3

    Final Inspection (Fire Alarm / Alternative Suppression Systems)

    Installation company representative must be present; fire alarm final additionally requires a 'System of Record Completion' from the alarm company plus an emailed monitoring-service report.

See the full Edgewood inspection guide — scheduling & re-inspection fees →

Tips

  • There is no combined sprinkler-plus-alarm fee line — a project installing both systems is billed separately under each schedule (e.g., $75 residential sprinkler + $150 commercial fire alarm).
  • Bring the SFCFD-stamped set of plans to every inspection — SFCFD will not perform an inspection without them on site.
  • Only Visa/MasterCard/Discover, check, money order, or cashier's check are accepted for plan review fees; SFCFD does not accept cash.

Frequently asked questions

Edgewood requires a fire sprinkler & fire alarm system permit (santa fe county fire department — fire prevention/risk reduction division) for: Three full-size sets of plans required for review, for both sprinkler systems (residential or commercial) and fire alarm/detection systems, plus cut sheets for all components/devices/appurtenances (SFCFD Fire Protection Systems Submittal & Inspection Guidelines); Commercial sprinkler plans additionally require hydraulic calculations and a design-area notation; fire alarm plans additionally require voltage-drop calculations, battery details/calculations, and a system inputs-and-outputs matrix; Plans must be stamped by a NICET Level III or IV technician AND a New Mexico-certified engineer or NM-certified Fire Protection Engineer (alternative fire suppression systems may instead be stamped by NICET III/IV or a NM Certified Fire Protection Engineer alone); Full payment is required before plans are accepted for review — accepted forms are Visa, MasterCard, Discover, check, money order, or cashier's check; cash is not accepted; The SFCFD-stamped set of plans must be present on site at every inspection, or the inspection will not be performed; Sprinkler systems require both a rough-in inspection and a final inspection; fire alarm and alternative suppression systems require a final inspection only; Both the fire alarm and sprinkler final inspections must be completed before a Certificate of Occupancy is released. If your project isn't listed, confirm with Town of Edgewood Planning & Zoning Department (Community Development Division) at (505) 286-4518 before starting work.

$150.00 for the plan review and permit, per SFCFD's published Fee Schedule for Fire Inspection & Plan Review, plus a $50.00 resubmission fee if the plans are rejected and must be resubmitted.

Edgewood does not publish a plan-review timeline for this permit. Contact Town of Edgewood Planning & Zoning Department (Community Development Division) at (505) 286-4518 for current turnaround.

You'll need: Fire Protection Systems Plan Submittal (SFCFD); Contractor's Material & Test Certificate for Above Ground Piping; System of Record Completion + Monitoring Service Report. Depending on your project, Edgewood may also ask for: Hydraulic Calculations & Design Area Notation; Voltage Drop / Battery Calculations & System I/O Matrix. See the required-documents checklist on this page for details on each.

Edgewood requires 3 inspection(s) for a fire sprinkler & fire alarm system permit (santa fe county fire department — fire prevention/risk reduction division), in order: Rough-in Inspection (Sprinkler), Final Inspection (Sprinkler), Final Inspection (Fire Alarm / Alternative Suppression Systems). Schedule each through Town of Edgewood Planning & Zoning Department (Community Development Division) ((505) 286-4518).

Apply through Town of Edgewood Planning & Zoning Department (Community Development Division) at 171-A State Rd. 344, Edgewood, NM 87015-3610. Phone: (505) 286-4518, email: codeenforcement@edgewood-nm.gov (Code Enforcement complaints only — Planning & Zoning has no separately published email as of 2026-07-18; the Town site routes contact through a web form). Call (505) 286-4518 for permit questions.. Office hours: Not published on the Town's Planning & Zoning page as of 2026-07-18 — call (505) 286-4518 to confirm current hours.. Official information: https://www.edgewood-nm.gov/planning-zoning.

Edgewood, New Mexico has adopted: 2015 International Fire Code (IFC) — the only building-related code the Town of Edgewood's own Planning & Zoning page lists as directly 'adopted by Town of Edgewood' in its Quick Links (edgewood-nm.gov/planning-zoning).; Edgewood is NOT a New Mexico Construction Industries Division (CID) Local Enforcement Agency (LEA) — unlike Albuquerque, Santa Fe, Las Cruces, and Rio Rancho, it has no building department of its own, so all structural/trade codes are enforced directly by the state CID under the statewide New Mexico Administrative Code (NMAC) Title 14 baseline, not a town-adopted amendment set. Per NM RLD/CID's Rules, Laws and Building Codes page (current as of the 2025-11-19 fee-page update) and CID's October 2024 Building Permit Guide for Residential Construction, CID currently enforces: 2021 New Mexico Commercial Building Code (NMAC 14.7.2) / 2021 International Building Code; 2021 New Mexico Residential Building Code (NMAC 14.7.3) / 2021 International Residential Code; 2021 New Mexico Earthen Building Materials Construction Code, Phase III (NMAC 14.7.4); 2009 New Mexico Non-Load-Bearing Baled Straw Construction Building Code, Phase III (NMAC 14.7.5); 2021 New Mexico Residential Energy Conservation Code (NMAC 14.7.6, effective 7/30/2024); 2021 New Mexico Existing Building Code (NMAC 14.7.7); 2021 New Mexico Historic Earthen Buildings code (NMAC 14.7.8); 2021 New Mexico Commercial Energy Code (NMAC 14.7.9); 2021 New Mexico Plumbing Code (NMAC 14.8.2) / 2021 Uniform Plumbing Code (IAPMO); 2012 New Mexico Swimming Pool, Spa, and Hot Tub Code (NMAC 14.8.3); New Mexico Medical Gas Code (NMAC 14.8.4); 2021 New Mexico Mechanical Code (NMAC 14.9.2) / 2021 Uniform Mechanical Code (IAPMO); 2012 New Mexico Solar Energy Code (NMAC 14.9.6); 2017 ICC/ANSI A117.1 Accessibility Code; 2020 New Mexico Electrical Code (NMAC 14.10.4) / 2020 National Electrical Code; and 2012 New Mexico Electrical Safety Code (NMAC 14.10.5).. Local amendments apply — see the Edgewood overview page for the full list.

The Santa Fe County Fire Department's Fire Prevention/Risk Reduction Division, not the Town of Edgewood. SFCFD's own website states it 'protects approximately 1900 square miles of unincorporated area as well as the incorporated Town of Edgewood,' and Edgewood has no fire marshal or fire-code enforcement office of its own.

Sources & verification

Verified against official sources. Last reviewed 2026-07-22.

Fees, timelines, and adopted codes are researched from each jurisdiction's published records — see how we verify. Requirements change and vary by project, so always confirm the current details with the Edgewood building department before you submit. PermitBase is an independent reference and is not affiliated with any government agency.