Fire Sprinkler System Permit in Herriman, Utah

Fire protection system permitting in Herriman is handled by Unified Fire Authority (UFA), a special fire district separate from the Herriman City Building Department. Herriman City is listed among UFA's member communities. UFA requires a permit for installation or modification of any automatic fire sprinkler system, plus mandatory third-party peer review of the design (except for minor work below specific device-count thresholds). UFA itself charges no permit fee for this — confirmed against UFA's own FY26/27 Adopted Budget, which itemizes the Fire Prevention division's entire fee revenue as Hazardous Materials & Tank Permits, Firewatch Reimbursements, and Fireworks Permits only. The applicant instead pays a privately-set fee directly to one of UFA's approved third-party peer-review firms.

Verified 2026-07-20 · Source

When you need this permit

  • Permit required from the fire code official (UFA) before beginning work on any fire protection system, per International Fire Code Section 105.1.1 — beginning work before permit issuance and plan approval is done at the contractor's own risk
  • Fire Sprinkler System plans must be submitted to a UFA-approved Third Party Review company before final submittal to UFA (ufaplansubmittal@unifiedfire.org)
  • Third-party peer review required for automatic fire sprinkler system installation/modification, EXCEPT: installation of fire hydrants/underground supply lines, pre-engineered kitchen hood suppression systems, or installation/relocation of fewer than 20 sprinkler heads
  • System designer must be NICET Level III (Water-Based Fire Protection Systems Layout) or better, a Fire Protection Engineer, or a licensed engineer with specific additional fire protection training
  • Design and installation per the most recent NFPA 13, 13-R, or 13-D adopted by the State of Utah
  • Systems with 20 or more sprinkler heads (with limited 13-D/13-R exceptions) require off-site remote monitoring from an approved monitoring company

Required documents

Check off what you have — your progress is saved on this device.

Not ready yet0 of 2 required documents checked.

This checker covers one permit. A full project usually triggers several — our paid checklist will assemble all of them, from $29

Fee schedule

UFA Plan Review / Permit Fee (fire sprinkler systems)Confirmed directly against UFA's FY26/27 Adopted Budget (unifiedfireut.gov/wp-content/uploads/ProposedBudget_040626.pdf), Fire Prevention division Revenue Summary, p.288: the division's complete FY27 fee revenue is broken out into exactly three categories — Hazardous Materials & Tank Permits ($370,000), Firewatch Reimbursements ($9,000), and Fireworks Permits ($6,000), totaling $385,000. No fire sprinkler or fire alarm permit fee line item exists anywhere in that revenue breakdown, confirming UFA itself does not bill a permit fee for these systems.
$0 — UFA charges no separate plan-review or permit fee
Third-Party Peer Review Fee (paid to private reviewer, not UFA)UFA's 'Peer Review for Fire Protection Systems' roster (unifiedfireut.gov/wp-content/uploads/Peer-Review-for-Fire-Protection-Systems-4.25.pdf) lists 10 UFA-approved private engineering firms/individuals (e.g., Protection Consultants Inc., Spectrum Engineers, Impact Fire Protection) and instructs applicants to 'submit plans to the company of your choice' — UFA does not set, collect, or publish this fee since it is a private commercial transaction between the applicant and the reviewer they select.
Not published — set independently by each approved third-party reviewer

Review timeline

Plan review
Not published — contact the department

How long did your Fire Sprinkler System Permit permit actually take in Herriman?

Anonymous — one question, no email. Answers are combined and only shown once at least 5 people have reported.

Inspection process

    See the full Herriman inspection guide — scheduling & re-inspection fees →

    Tips

    • Fire sprinkler permitting in Herriman runs through Unified Fire Authority (UFA), NOT the Herriman City Building Department — Herriman's own Master Fee Schedule has no fire sprinkler permit fee line item because UFA handles this separately.
    • UFA itself charges no plan-review or permit fee for fire sprinkler systems — confirmed by UFA's FY26/27 Adopted Budget, which lists the Fire Prevention division's entire fee revenue (Hazmat & Tank Permits, Firewatch, Fireworks Permits) with no sprinkler/alarm line item. The real cost to the applicant is the market rate charged by whichever UFA-approved third-party peer reviewer they hire.
    • Herriman's Master Fee Schedule 'Fire Impact Fee' ($0.43/sq ft non-residential, per the Commercial Building Permit entry in this file) is a development impact fee unrelated to the sprinkler system installation permit itself.
    • Design and third-party peer review must be completed BEFORE final plans go to UFA — starting sprinkler work before permit issuance and plan approval is done at the contractor's own risk with no special allowances.
    • Any change to a fire sprinkler system's hazard classification design requires a new permit and a new third-party plan review.

    Frequently asked questions

    Herriman requires a fire sprinkler system permit for: Permit required from the fire code official (UFA) before beginning work on any fire protection system, per International Fire Code Section 105.1.1 — beginning work before permit issuance and plan approval is done at the contractor's own risk; Fire Sprinkler System plans must be submitted to a UFA-approved Third Party Review company before final submittal to UFA (ufaplansubmittal@unifiedfire.org); Third-party peer review required for automatic fire sprinkler system installation/modification, EXCEPT: installation of fire hydrants/underground supply lines, pre-engineered kitchen hood suppression systems, or installation/relocation of fewer than 20 sprinkler heads; System designer must be NICET Level III (Water-Based Fire Protection Systems Layout) or better, a Fire Protection Engineer, or a licensed engineer with specific additional fire protection training; Design and installation per the most recent NFPA 13, 13-R, or 13-D adopted by the State of Utah; Systems with 20 or more sprinkler heads (with limited 13-D/13-R exceptions) require off-site remote monitoring from an approved monitoring company. If your project isn't listed, confirm with Herriman City Building Department at (801) 446-5327 before starting work.

    In Herriman, the published UFA Plan Review / Permit Fee (fire sprinkler systems) is: $0 — UFA charges no separate plan-review or permit fee. Additional published fees: Third-Party Peer Review Fee (paid to private reviewer, not UFA) — Not published — set independently by each approved third-party reviewer. These are the jurisdiction's own published figures — see the fee schedule table and source citations on this page.

    Herriman does not publish a plan-review timeline for this permit. Contact Herriman City Building Department at (801) 446-5327 for current turnaround.

    You'll need: Fire Sprinkler System Plans; Third Party Peer Review Report. See the required-documents checklist on this page for details on each.

    Apply through Herriman City Building Department at 5355 W Herriman Main St, Herriman, UT 84096. Phone: (801) 446-5327, email: building@herriman.gov. Office hours: Mon–Fri 7:30 AM – 5:30 PM (call before 4:00 PM for inspection requests). Official information: https://www.herriman.gov/building/.

    Herriman, Utah has adopted: 2021 International Residential Code (IRC), including amendments to the 2021 Residential Energy Code and Appendix AE & AQ — Herriman City Building Codes and Design Criteria (herriman.gov/building-codes-design-criteria, live-checked 2026-07-16); REMAINS CURRENT, Utah Code § 15A-2-103(1)(b) did NOT change this edition in the 7/1/2026 amendment. CORRECTION (2026-07-16): a prior version of this entry read 'Appendix E & Q' — the city's page actually reads 'Appendix AE & AQ,' which correctly maps to Appendix AQ (§ 15A-2-103(1)(c)) and, subject to § 15A-2-104(1), Appendix AE (§ 15A-2-103(1)(k)); corrected to match the source verbatim.; Residential provisions of the 2024 International Swimming Pool & Spa Code (ISPSC) — CURRENT statewide as of 7/1/2026 per Utah Code § 15A-2-103(1)(n), superseding the 2021 ISPSC. Herriman's Building Codes and Design Criteria page still lists 'Residential provisions of the 2021 International Swimming Pool & Spa Code (ISPSC)' verbatim — live-checked 2026-07-16, confirming this one item lags. The statute controls.; 2024 International Energy Conservation Code (IECC), single unsplit statewide edition — CURRENT as of 7/1/2026 per Utah Code § 15A-2-103(1)(h) (no residential/commercial split under current law). Herriman's own page (live-checked 2026-07-16) already lists '2024 Commercial IECC' for the commercial side, but for residential energy it instead cites 'Amendments to the 2021 Residential Energy Code' rather than the unified 2024 IECC — that residential-specific citation is superseded by the single 2024 IECC under current law; preserved as history in the HISTORY entry below.; HISTORY (superseded 7/1/2026, but still shown on Herriman's own page as of live-check 2026-07-16): 'Amendments to the 2021 Residential Energy Code' — Herriman City Building Codes and Design Criteria; no longer has independent authority for residential energy provisions now that Utah Code § 15A-2-103(1)(h) applies a single unsplit 2024 IECC to both residential and commercial construction statewide.; 2023 National Electrical Code (NEC) — Herriman City Building Codes and Design Criteria (live-checked 2026-07-16, unchanged); also Utah Code § 15A-2-103(1)(g); REMAINS CURRENT, UNCHANGED by the 7/1/2026 amendment; 2024 International Building Code (IBC), including Appendix C & J — Herriman City Building Codes and Design Criteria, live-checked 2026-07-16: the city's own page is ALREADY CURRENT, verbatim listing '2024 International Building Code (IBC), including Appendix C & J,' matching Utah Code § 15A-2-103(1)(a) effective 7/1/2026. This file's prior codesAdopted entry (2021 IBC) was the stale one.; 2024 International Plumbing Code (IPC) — Herriman City Building Codes and Design Criteria, live-checked 2026-07-16: the city's own page is ALREADY CURRENT, matching Utah Code § 15A-2-103(1)(d). This file's prior codesAdopted entry (2021 IPC) was the stale one.; 2024 International Mechanical Code (IMC) — Herriman City Building Codes and Design Criteria, live-checked 2026-07-16: the city's own page is ALREADY CURRENT, matching Utah Code § 15A-2-103(1)(e). This file's prior codesAdopted entry (2021 IMC) was the stale one.; 2024 International Fuel Gas Code (IFGC) — Herriman City Building Codes and Design Criteria, live-checked 2026-07-16: the city's own page is ALREADY CURRENT, matching Utah Code § 15A-2-103(1)(f). This file's prior codesAdopted entry (2021 IFGC) was the stale one.; 2024 International Fire Code (IFC) — Herriman City Building Codes and Design Criteria, live-checked 2026-07-16 (the city's own page now reads '2024 International Fire Code (IFC),' up from the 2021 edition in this file's prior entry). NOTE: the IFC is NOT among the codes adopted by Utah Code § 15A-2-103 (Title 15A Chapter 2, State Construction Code) — Utah's Fire Code is separately adopted under Title 15A Chapter 5, State Fire Code Act; the city's own edition choice is left as published, no statutory edition change applies via § 15A-2-103.; Commercial provisions of the 2024 International Energy Conservation Code — Herriman City Building Codes and Design Criteria, live-checked 2026-07-16 (already updated from the 2021 edition in this file's prior entry); collapses into the single unsplit 2024 IECC entry above per Utah Code § 15A-2-103(1)(h), which no longer distinguishes residential/commercial editions.; 2024 International Existing Building Code (subject to HUD & IRC Appendix E) — Herriman City Building Codes and Design Criteria, live-checked 2026-07-16: the city's own page is ALREADY CURRENT, matching Utah Code § 15A-2-103(1)(i). This file's prior codesAdopted entry (2021 IEBC) was the stale one.; Modular Building Institute (MBI) Standards 1200 and 1205 — statewide per Utah Code § 15A-2-103(1)(o); not listed on Herriman's own Building Codes and Design Criteria page (live-checked 2026-07-16), added here per statute.; ICC/ANSI A117.1-2009 and A117.1-2017 — Herriman City Building Codes and Design Criteria; Applicable Utah State Amendments — Utah Code Title 15A; NOTE (2026-07-16 re-verification): Utah Code § 15A-2-103, version effective 7/1/2026 (superseded 1/1/2027), took effect 15 days before this re-verification. IBC/IPC/IMC/IFGC/IECC/IEBC/residential ISPSC are now 2024 statewide; IRC (2021) and NEC (2023) did NOT change. Herriman's Building Codes and Design Criteria page (herriman.gov/building-codes-design-criteria) was live-checked 2026-07-16 via real-browser navigation. UNLIKE most sibling cities checked in this pass, Herriman's page is ALREADY CURRENT for IBC/IPC/IMC/IFGC/IEBC/commercial-IECC (all show 2024) — this file's PRIOR codesAdopted data (2021 for all of these) was the stale one, not the city. The only genuine city-side lag found: the ISPSC residential-provisions citation still reads 2021 (should be 2024), and the residential-energy citation still points to 'Amendments to the 2021 Residential Energy Code' rather than the unified 2024 IECC that now governs both residential and commercial per § 15A-2-103(1)(h). IRC and NEC editions are correct on both the statute and the city's page.. Local amendments apply — see the Herriman overview page for the full list.

    Unified Fire Authority (UFA), a special fire district that lists Herriman City among its member communities, handles fire sprinkler system permitting — not the Herriman City Building Department.

    Yes, in most cases. UFA requires a third-party peer review of automatic fire sprinkler system plans before final UFA review, except for installation or relocation of fewer than 20 sprinkler heads, fire hydrant/underground supply line work, and pre-engineered kitchen hood suppression systems.