Fire Alarm System Permit — Millcreek, Utah · Requirements sheet
Reviewed 2026-07-21 · Source: https://unifiedfireut.gov/prevention/plan-reviews/
PermitBase is an independent reference and is not affiliated with any government agency. Requirements change and vary by project — confirm current details with the building department before you submit.
Fire Alarm System Permit in Millcreek, Utah
Millcreek is served by the Unified Fire Authority (UFA), which acts as the fire code official under International Fire Code (IFC) Sections 104.7.2 and 105.1.1. Per UFA's own Fire Alarm and Detection System Submittal guide, 'All new commercial fire alarm system installations and existing system additions or modifications require a plan submittal and permit from UFA' — this permit is issued and administered entirely by UFA, not by the Millcreek Building Department. Neither Millcreek's own FY25 Consolidated Fee Schedule nor UFA's own published Fee Schedule 2025 lists a specific dollar fee for this permit type (both checked in full); when a fire alarm system is installed as part of new construction or a tenant improvement, Millcreek's separate valuation-based Building Permit fee (see the Commercial Building Permit and Commercial Tenant Improvement / Alteration Permit entries) still applies to the overall project.
Reviewed 2026-07-21 · Source
When you need this permit
- All new commercial fire alarm system installations and existing system additions or modifications require a plan submittal and permit from UFA
- Design and installation via the most recent version of NFPA 72 adopted by the State of Utah
- System designer must be NICET Level III or better (Engineering Technician), a Fire Protection Engineer, or a licensed engineer with specific additional fire protection system training
- Any structure (except one- and two-family dwellings) with 20 or more fire sprinkler heads installed must also have off-site alarm monitoring
Required documents
Check off what you have — your progress is saved on this device.
Not ready yet — 0 of 3 required documents checked.
This checker covers one permit. A full project usually triggers several — our paid checklist will assemble all of them, from $29 →
Fee schedule
Review timeline
Inspection process
- 1
Rough-In
Device and wiring placement verified against approved plans before wall cover, including notification appliance (horn/strobe) locations.
- 2
Battery / Standby Power Test
Battery calculations and standby power supply verified per submitted plans.
- 3
Final Acceptance Test / Record of Completion
Full functional test of devices and notification appliances, remote annunciator check, and — for Institutional, Hazardous, Large Shopping Mall, and High-Rise occupancies — verification of the required Knox brand 1300 series cabinet with building floor plans and utility shut-off information.
See the full Millcreek inspection guide — scheduling & re-inspection fees →
Tips
- Fire alarm systems in Millcreek are permitted and inspected entirely by the Unified Fire Authority (UFA), not the Millcreek Building Department — UFA's own guide states plainly that all new commercial fire alarm installations and modifications require a plan submittal and permit from UFA.
- Adding or relocating 5 or more horn/strobe notification appliances triggers the third-party peer review requirement (a UFA permit is still required below that threshold).
- Neither Millcreek's nor UFA's published fee schedule lists a specific dollar fee for this permit — confirm current pricing directly with UFA Fire Prevention, (801) 743-7200, before applying.
- Unfinished tenant spaces must have at least one horn/strobe device per unit; restrooms require strobe-only devices per UFA's submittal guide.
- When a fire alarm system is installed as part of new construction or a commercial tenant improvement, Millcreek's own valuation-based Building Permit fee still applies to that overall project — the UFA process is an additional required sign-off, not a substitute.
Frequently asked questions
Sources & verification
Key facts verified against official sources. Last reviewed 2026-07-21.
Fees, timelines, and adopted codes are researched from each jurisdiction's published records — see how we verify. Requirements change and vary by project, so always confirm the current details with the Millcreek building department before you submit. PermitBase is an independent reference and is not affiliated with any government agency.
Other permits in Millcreek
Fire Alarm System Permit in other cities
Compare fire alarm system permit fees across Utah →
Look up this fee in a different city →
Now live
Build your Millcreek project checklist
Describe your project once and get every permit, document, and fee it triggers in Millcreek — in one checklist. Sign up and pay once to generate it, or go unlimited with Pro.
Get started →